Eidis Medium Temperature Series 4 Drop-In Packaged Refrigeration Units

Drop-in, Push-in & Slide-in Packaged Coldroom Refrigeration Systems

  • Standard power requirement 220/240 volt 50/HZ.
  • Easily installed.
  • Units are provided with electrical cable and 3 pin plug.
  • Reliable, safe operation.
  • Controls of conventional design, unaffected by voltage spikes.
  • Drop-In & Slide-In models have cross ambient temperature controls factory set 2°C to 3°C room temperature. PI Global model electonic controls, with LED display. Adjustable by user.
  • Dual pressure control with manual or auto reset on high cut out to protect against condenser airflow restriction on Drop-in and Slide-in Models.
  • Vibration free balanced external rotor fans.
  • Baseplate powder coated.
  • Moulded white a.b.s. insulated inner panel.

Features

  • Both heat exchange coils use rifle bore tubing.
  • Accurate metal pressing by C.N.C. Turret.
  • Compact construction minimising freight cost.
  • Bench tested before packaging.
  • Each system has an installation instruction sheet, a unit to coldroom sealing strip, electronic componentry usage instructions where required and a drawing showing cut out dimensions and positioning.
  • Specifications
  • Technical Data
  • Dimensions
Model No. Compressor Watts Capacity
@ +2°C Room Temp.
Evap. Kth Grams
Model Nominal HP R404a Charge
66/4 6215GK 1/2 1300 5 700
68/4 6226GK 1+ 1940 6.8 700
88/4 9232GK 1-1/4 2280 7 800
1212/4 9238GK 1-1/2 3220 6 1550
2012/4 MTZ28 2-1/4 4200 5 3000
Model No. Compressor Condenser Fan Evaporator Fan Standard Evap Unit
Model Amps Qty x Fan Dia Standard
Qty x Fan Dia
Low-Profile
Qty x Fan Dia
Amps
RLA* LRA RLA* MRA*
64/4 6210GK 3.23 19.00 1 x 254mm N/A 2 x 178 3.95 4.11
66/4 6215GK 3.78 22.00 1 x 275mm 1 x 300mm 4.65 4.94
67/4 6222GK 4.95 37.00 1 x 300mm N/A 3 x 178 6.02 6.33
68/4 6226GK 5.09 27.50 1 x 300mm N/A 5.95 6.44
88/4 9232GK 5.12 43.00 1 x 300mm 1 x 300mm 6.00 7.84
1212/4 9238GK 8.10 43.00 1 x 350mm 1 x 350mm N/A 9.50 10.76
2012/4 MTZ28 10.69 58.00 1 x 350mm 2 x 300mm N/A 12.25 13.45

Notes
• The Manufacturer reserves the right to change specifications as necessary without notice.
• * – Unit and Compressor RLA data are taken at +2°C room temp +32°C ambient condition. (+/-5%)
• * – Unit MRA data are based on compressor MRA + fan RLA. (+/-5%)

 

Medium Temperature & Low Temperature EIDIS Drop-In Packaged Refrigeration Units Dimensions

Model No. Packaged Dimensions Weight
Kg
Unit Dimension
L W H A B C D E F G H
66/4 720 460 990 52 310 80 685 605 400 230 16 370
68/4 720 460 1060 6.61 380 80 685 605 400 230 16 370
88/4 720 460 1060 67 380 80 685 605 400 230 16 370
1300 LT 720 460 1150 67 380 170 685 605 400 230 16 370
1212/4 970 680 1120 120 375 80 890 762 590 298 16 450
2500 LT 970 680 1210 120 375 170 890 762 590 298 16 450
2012/4 1440 920 1370 180 670 80 1285 1215 545 450 820 435

Notes
• The Manufacturer reserves the right to change specifications as necessary without notice.
• LT = Low Temperature